Control Valve Sizing and Selection

Control Valve Sizing and Selection

Control Valve Sizing and Selection

Enter up to six operating conditions — minimum / normal / maximum are included by default, plus three optional alternatives (tick include to add them) — and read the required Cv, choked-flow status and resulting valve travel of each enabled case off one selected valve, so the opening range stays inside a controllable band. Every result and chart the single‑case calculator gives is available per condition.

Cv · Kv · travel %  |  up to 6 cases · choked flow · cavitation · noise · turndown check · liquid‑gas mixtures
Service
Units
Export
Valve Specification

FL and xT are set automatically from the valve type. Replace with the certified trim datasheet for final selection.

1.000

Globe ≈ 50, ball ≈ 100.

Process data
Basis of calculation.
  • Viscous liquids: Cv = Cvturbulent / FR, with FR from the valve Reynolds number (ISA‑75.01.01 Annex A). Turbulent at Rev ≥ 40 000, so water duties are uncorrected; heavy oils raise the required Cv.
  • Liquid: Cv = (Q / (Fp · N1)) · √(Gf / ΔP), with choked limit ΔPchoked = FL² · (P1 − FF · Pv), FF = 0.96 − 0.28√(Pv/Pc). Flashing uses the isenthalpic steam-table flash across the outlet; the expanded two‑phase volume sets the outlet velocity.
  • Gas / steam: Cv = W / (N8 · Fp · P1 · Y · √(x·M / (T1·Z))), Y = 1 − x / (3 · Fk · xT), choked when x ≥ Fk·xT.
  • Liquid‑gas mixtures use Fisher Catalog 12 §2 (eq. 1): Cvr = (Cvl + Cvg)(1 + Fm) — both phases are sized separately through the valve, and Fm comes off Figure 1 at the inlet gas volume ratio Vr = Vg/(Vl + Vg) (the gas volume carrying the compressibility factor Z). It collapses onto the single‑phase equations at both ends: no gas gives the liquid answer, no liquid gives the gas answer.
  • Travel from the inherent characteristic Cv/Cvrated = f(h, R): linear f = h, equal‑percentage f = Rh−1, quick‑opening f = √h.
  • Valve size is selected once, from the LARGEST case (Cv × margin, keeping the worst travel ≤ max travel). All other cases are then turndown conditions on that valve. Noise (IEC 60534‑8‑3 aerodynamic / ‑8‑4 hydrodynamic), choked flow, flashing and the recommended downstream size are evaluated per condition in the detail panel.
  • Rated capacities come from the Lapar catalog tables (High precision / High capacity curve). FL and xT follow the owner FL/XT reference table (single-row values, not size-dependent) — confirm against the certified trim datasheet, plus actuator, materials and shut‑off class.

References: ANSI/ISA‑75.01.01‑2012 · IEC 60534‑2‑1:2011 · IEC 60534‑8‑3:2010 (aerodynamic) · IEC 60534‑8‑4:2015 (hydrodynamic) · ISO 13703 / API RP 14E (two‑phase erosion)